Gordon Piatt Parts

Oil Metering Valves

Gordon-Piatt Oil Metering Valves
Number Description
350600-0300 3/8" Oil Metering Valve S-3-3TW1
350600-0301 3/8" Oil Metering Valve S-3-5TW1
350600-0302 3/8" Oil Metering Valve S-3-7TW1
350600-0303 3/8" Oil Metering Valve S-3-9TW1
350600-0304 3/8" Oil Metering Valve S-3-11TW1
350600-0305 3/8" Oil Metering Valve S-3-13TW1
350600-0306 3/8" Oil Metering Valve S-3-1610TW1
350600-0402 1/2" Oil Metering Valve B-.50-18TW1
350600-0400 1/2" Oil Metering Valve B-.50-20TW1
350600-0401 1/2" Oil Metering Valve B-.50-24TW1

 

Gordon Piatt Oil Metering Valve

The John Zink 3/8" metering valves 935000-0511, 935000-0513, and 935000-0520 are no longer available.

Gordon Piatt Oil Metering Valve

Adjustment Procedure

Valves vary by the amount of rotation required to cover the full range of regulation. Most valves will have a range of regulation. Most valves will have a range from 0° to 90° or 0° to 120°. The maximum travel that can be realized from a 90° actuator and mechanical linkage arrangement is about 120°. The amount of travel to be used is dependent upon the required turn-down ratio (flow rates) between high-fire and low-fire and the flow characteristics of the particular valve.
 

For initial start-up: (use factory set points)


Adjustment requirements cannot be finally established until after the burner is fired. The valve should work from a mid-open to a closed position when located in the return line when going from low-fire to high-fire.

To adjust amount of travel, loosen base of ball-joint connector located in slotted actuator arm and reposition to desired setting, then re-tighten connector.

A = Decrease travel of metering valve
B = Increase travel of metering valve
C = Increase travel of metering valve
D = Decrease travel of metering valve
E = Quickens travel first 1” of movement
F = Slows travel first 1” of movement

Up to top

Burner technology of Gordon-Piatt Energy Group, Inc. was purchased by John Zink Company, LLC, in October 2000.  In 2009, a decision was made that the John Zink Company, LLC. will discontinue production of all Gordon-Piatt burners.  Cici Boiler Rooms, Inc. is not a factory-authorized distributor of John Zink Gordon-Piatt brand products.