Gordon-Piatt Oil Metering
Valves |
|
Number |
Description |
|
350600-0300 |
3/8" Oil Metering Valve S-3-3TW1 |
|
350600-0301 |
3/8" Oil Metering Valve S-3-5TW1 |
|
350600-0302 |
3/8" Oil Metering Valve S-3-7TW1 |
|
350600-0303 |
3/8" Oil Metering Valve S-3-9TW1 |
|
350600-0304 |
3/8" Oil Metering Valve
S-3-11TW1 |
|
350600-0305 |
3/8" Oil Metering Valve
S-3-13TW1 |
|
350600-0306 |
3/8" Oil Metering Valve
S-3-1610TW1 |
|
350600-0402 |
1/2" Oil Metering Valve
B-.50-18TW1 |
|
350600-0400 |
1/2" Oil Metering Valve
B-.50-20TW1 |
|
350600-0401 |
1/2" Oil Metering Valve
B-.50-24TW1 |
|
 |
The John
Zink 3/8" metering valves 935000-0511,
935000-0513, and 935000-0520 are no longer
available.
 |
Adjustment
Procedure
Valves vary by
the amount of rotation required to
cover the full range of regulation.
Most valves will have a range of
regulation. Most valves will have a
range from 0° to 90° or 0° to 120°.
The maximum travel that can be
realized from a 90° actuator and
mechanical linkage arrangement is
about 120°. The amount of travel to
be used is dependent upon the
required turn-down ratio (flow
rates) between high-fire and
low-fire and the flow
characteristics of the particular
valve.
For initial
start-up: (use factory set points)
Adjustment requirements cannot be
finally established until after the
burner is fired. The valve should
work from a mid-open to a closed
position when located in the return
line when going from low-fire to
high-fire.
To adjust amount
of travel, loosen base of ball-joint
connector located in slotted
actuator arm and reposition to
desired setting, then re-tighten
connector.
A = Decrease travel of
metering valve
B = Increase travel of
metering valve
C = Increase travel of
metering valve
D = Decrease travel of
metering valve
E = Quickens travel
first 1” of movement
F = Slows travel first
1” of movement |
|
Up to top
Burner
technology of Gordon-Piatt Energy Group,
Inc. was purchased by John Zink Company,
LLC, in October 2000. In 2009, a
decision was made that the John Zink
Company, LLC. will discontinue production of
all Gordon-Piatt burners. Cici Boiler
Rooms, Inc. is not a factory-authorized
distributor of John Zink Gordon-Piatt brand
products.
|